Page 34
SECONDARY ALARMS TO OUTPUT OPTIONS - P561E - P568E
In this block of addresses P561E relates to output #1, P562E relates to output #2 etc
P561E 1E = Zone Tamper Alarm to Output #1
2E = System Tamper Alarm to Output #1
3E = Mains Failure to Output #1
4E = Panel Battery Low to Output #1
5E = Telephone Line Failure to Output #1
6E = Dialler Failure to get a Kiss-off to Output #1
7E = Automatic Pulse to Output #1
8E = 24 Hour Smoke Reset to Output #1
Option 1 Zone Tampers to Output - When a zone tamper alarm occurs this address is used to map the Zone
Tampers to an output.
Option 2 System Tamper Alarm to Output - This option is used to map activations of the common Tamper
Input to an output. This common tamper input is normally used to monitor the panel cabinet and
satellite tamper switches.
Option 3 Mains Failure To Output - A mains failure will be indicated at the output when this option is enabled.
The Alarm Reset Timer for this output must be set to “0”.
Option 4 Panel Battery Low to Output - A battery Low condition will be indicated at the output when this option
is enabled. The Alarm Reset Timer for this output must be set to “0”.
Option 5 Telephone Line Failure to Output - A telephone line failure will be indicated at this output when the
option is enabled. When the line restores this output will return to normal. Set the reset time to “0”.
Option 6 Dialler Failure to get a Kiss-off to Output - If the dialler reaches its maximum dialling attempts for an
alarm condition and is not kissed off, this failure will be indicated at the output. When this alarm event
is accessed via Memory Mode at any keypad the output will reset back to normal. Set the reset time to
“0”.
Option 7 Automatic Pulse to Output - This option will cause the output to pulse (at a rate set by the pulse timer
for the output) every 5 seconds. It is primarily designed to flash an external light to show that the alarm
is still active (reassurance indication).
Option 8 24 Hour Smoke Reset to Output - This option will cause the output to pulse for 2 seconds on arming
of any Area following a 24 Hour zone alarm. It is designed to allow automatic reset of hardwired,
latching smoke detectors following an alarm.
OUTPUT LOCAL PA MESSAGE OPTIONS - P571E-P578E
P571E 1E = Enable Local PA Output #1 ON message
2E = Use Canned Local PA Output #1 ON message
3E = Repeat Local PA Output #1 ON message
4E = Spare
5E = Enable Local PA Output #1 OFF message
6E = Use Canned Local PA Output #1 OFF message
7E = Repeat Local PA Output #1 OFF message
8E = Spare
Option 1 Enable Local PA Output ON message. When the Output is turned ON, it is possible to play a pre-
recorded speech message via the panels internal speaker. With this option on the panel is expecting a
customised message to be programmed by the installer and the message numbers selected at
addresses P891E-P898E, if no message number is programmed, the panel will not play any local PA
message when the Output turns ON.
Option 2 Use Canned Local PA Output ON message. If option 1 above is on plus this option, the panel will
play the default “Canned” audio message when the Output turns ON provided there is no value set at
addresses P891E-P898E.
Option 3 Repeat Local PA Disarm message. If option 1 or 2 or both are on above and this option is on, the