47
System Setup
Menu Item
77 78
See pages
to
E-mail Setting
* The e-mail
function is
included in
an option
sold
separately,
where
combined
with the Web
function.
Item
Validity/Invalidity of e-mail function
SMTPServer
Sending
Conditions
E-mail
Description
Setting of Invalidity does not allow
sending e-mails.
Specifies URL (IPaddress) of the
SMTP server.
Specifies a port number of the SMTP
server.
Whether to access in advance the POP
server specified before sending mail.
Specifies URL (IPaddress) of the POP
server.
Specifies a port number of the POP
server.
User ID used for POP authentication
Pass word used for POP authentication
Specifies destination groups to which
an e-mail will be sent at a time of
malfunction.
Specifies a time interval to retry sending
an e-mail when the malfunction has not
been cleared. (setting range : 1-72
hours, steps : one hour)
Specifies a string of characters
displayed in the Subject column when
the e-mail is received.
Specifies e-mail addresses
Omissible
SMTP Server Address
SMTP Server Port Number
Validity / Invalidity of [POP
before SMTP] option
Setting items
when [POP
before SMTP]
is valid
Sent-to Groups
Sending Interval
ITC Identification Name
Mail Address 1, 2, 3
POP Sever Address
POP Server Port
Number
POP User ID
POP Password
Operation
(Reference)
Description
This option is used to, when the Intelligent Touch Controller detects a malfunction in
such as the air-conditioning unit (*1), send an e-mail containing the date, the error
code and so on to the pre-registered administrators at three different addresses
maximum.
*1 : Where the malfunction refers a malfunction that occurs in the air- conditioning unit
or other facilities.
When a communication error between the Intelligent Touch Controller and the
air-conditioning unit or other facilities occurs, no e-mail will be sent.
If the warning of the air-conditioning unit occurred during a test run is defined to be
handled as a malfunction, the e-mail about such warning will be sent.
To use the e-mail function, the following equipment is required :
SMTP (Simple Mail Transfer Protocol) server
a server which can transfer the e-mails complying with RFC821
e-mail receiving terminal
a terminal which can receive the e-mails complying with RFC822
The system configuration is drawn in the figure below :
Internet
In this setting procedure, the following items are set.
SMTP server
Intelligent Touch Controller
Ethernet
(10BASE-T)
Send an e-mail
when a malfunction
occurs
e-mail receiving
terminal

Table of Contents