System Setup
Menu Item
77 78
See pages
to
Operation
(Reference)
Description
48
Timing of E-mail Sending
Referring to the figure below, timing of sending e-mails is described.
[Send when a malfunction occurs in the normal state]
If a malfunction occurs in the destination groups defined in the e-mail sending, wait
three minutes from the malfunction ( 1 in the figure below) before sending an e-mail.
* An e-mail will not be sent immediately after the first malfunction.
During the waiting time of three minutes, if another malfunction occurs in different
groups ( 2 or 3 in the figure below), one e-mail containing such multiple malfunctions
will be sent.
[Resend after sending once]
As shown in case of Group B, if the malfunction persists even after the sending time
interval from the first mail sending has elapsed, another e-mail will be sent.
In the group for which the e-mail has been sent, after recovering from the malfunction,
if another malfunction occurs again ( 5 in the figure below), the latest malfunction will
be sent after the sending time interval will have elapsed.
During the sending time interval, if a new malfunction occurs ( 4 in the figure below),
an e-mail will be sent after the sending time interval will have elapsed.
When the sending time interval has elapsed, if no malfunction is found in the groups,
the system will move from the resend state to the normal state.
* : The mark represents occurrence of a malfunction and the mark
represents recovery from the malfunction.
Group B
Group D
Resend state
i
Figure : Timing of E-mail Sending
Group A
1
2
5
Group C
4
3
Normal
state
Normal
state
Sending time
interval
Sending time
interval
3 minutes from
occurrence of
the malfunction
(wait for sending)
Send the malfunctions
occurred in Group A, B, C
Send the malfunctions
occurred in Group B, C, D
Group B : The malfunction
persists.
Group C : The malfunction has
occurred again.
Group D : Another malfunction
has occurred.
If no malfunction is
found, the system
will send no e-mail
and go back to the
normal state to start
monitoring the
air-conditioning unit.