Compressor Status
Description
Trigger Method Troubleshooting
Verificationonpage73.
l
Verifythesolenoidactuators.RefertoSection4.6.3SolenoidVerificationonpage73.
l
VerifytheSerialDriver.RefertoSection4.26.3SerialDriverVerificationonpage217.
l
ReviewthefaultlogforactualInvertertemperatureandotherconditionsthatare
recordedatthetimeoffault.
l
TheInverterrequiresreplacementiftheembeddedtemperaturesensorisdetermined
faulty.
HighDischarge
TemperatureFault
AFT
l
Suggestsinsufficientcharge(i.e.,lowgas),thecondensertemperaturehasincreased,
checkvalvehasfailedtoopenorthecompressorhasbeenrunninginsurgecondition
foranextendedperiodoftime.
l
Checkthechillergascharge,enteringcondenserair/waterconditionsandoperational
settings.
l
Verifycheckvalveopensduringcompressoroperation.
l
Verifythedischargepressure/temperaturesensor.RefertoSection4.32.3
Pressure/TemperatureSensorVerificationonpage246.
l
Reviewthefaultlogforactualdischargetemperatureandotherconditionsthatare
recordedatthetimeoffault.
LowSuctionPressure
Fault
DFT
l
Suggestsinsufficientcharge,insufficientsystemload,orasuddendropinevaporator
enteringair/watertemperatureorflow.
l
Checkthecharge,systemloadandenteringair/waterconditions.
l
Reviewthefaultlogforactualsuctionpressureandotherconditionsthatarerecordedat
thetimeoffault.
HighDischarge
PressureFault
AFT Consequence:
l
ResultsinanInstantaneousLock-OutFault-pre-CC4.0.0
Recommendation:
l
Suggeststhecondensermaybefaultyorinsufficientair/waterflow.
l
Checkthecondenserandair/waterflow.
l
Reviewthefaultlogforactualdischargepressureandotherconditionsthatarerecorded
atthetimeoffault.
3-PhaseOver-Current
Fault
AFT Consequence:
l
Duringstartupmode,allalarmsareignoredbythecontrolsystem,butfaultsarenot.
Therefore,whentheFLAcurrent(3-PhaseAlarmLimit)isreached,thecompressorwill
continuetoaccelerateifstartuprequirementsarenotsatisfied.AfterStartupis
complete,alarmswillslowthecompressorspeed.ResultsinanInstantaneousLockOut
Fault-pre-CC4.0.0.
Requiresapowercycletoreset.
l
Indicatesthecompressorisdrawingcurrentgreaterthanthe3-PhaseCurrentFault
Limit.
Recommendation:
l
Reviewthefaultlogforrecorded3-PhaseCurrentlevel,demand,enteringair/water
temperature(ifavailable)andotherconditionsthatarerecordedatthetimeoffault.
l
Usualcausesarestartspeedsettoohigh,minimumpressureratiosettoohighatstart-
up,powercontrolintegral(loop)gainsettoohigh.Canalsoberelatedtosudden
increaseinload/demandorsystemchanges.
HighCavity
TemperatureFault
AFT Consequence
l
Indicatesthemotorcoolingisinsufficient.
CAUTION:RepeatedoccurrencesofthisfaultcanresultinshaftdemagnetizationorBackEMFislow
Page 256 of 294 - M-SV-001-EN Rev. H 1/23/2023