Table 39. Expansion cards thermal limitation
Thermal Cooling
Tier level
Bus width Full height Cards Application
Restriction
(Conguration
Type / PCIe slot)
Half height Cards Application
Restriction
(Conguration
Type / PCIe slot)
5 x8 - Rear HDD Module
Conguration /
Slot# 2
QLOGIC 10G Dual
port BT, QLOGIC
25G Dual port SFP
1 Buttery Riser
Conguration /
Slot# 3, 4, 5
2 Rear HDD
Module
Conguration /
Slot# 2, 3
3 No Riser, No
Rear HDD
Module / Slot#
5
6 Mellanox 40G Dual
Port CXP, QSFP,
Solarare 10G Dual
Port SF852P,
Solarare 10G Dual
Port SF852X
Mellanox 40G Dual
Port CXP QSF,
Solarare 10G Dual
Port SF852X,
Solarare 10G Dual
Port SF852P
1 Buttery Riser
Conguration /
Slot# 3, 4, 5
2 Rear HDD
Module
Conguration /
Slot# 2, 3
10 QLOGIC 10G Quad
port QLGX
QLOGIC 10G Quad
port QLGX
1 Buttery Riser
Conguration /
Slot# 3, 4
2 Rear HDD
Module
Conguration /
Slot# 2, 3
8 x4 - - Intel NVME P4800X Buttery Riser
Conguration /
Slot# 3
Particulate and gaseous contamination specications
The following table denes the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specied limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the customer.
Table 40. Particulate contamination
specications
Particulate contamination Specications
Air ltration Data center air ltration as dened by ISO Class 8 per ISO 14644-1 with a
95% upper condence limit.
NOTE: This condition applies to data center environments only. Air
ltration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an oce or
factory oor.
Technical specications 185