Fault
Name
Fault Descriptions
Corrective Actions
Over-current during
acceleration:
. Short-circuit at motor
output.
. Torque boost too
high.
. Acceleration time too
short.
. AC drive output
capacity is too small.
. Check for possible poor insulation at the
output line.
. Decrease the torque boost setting in
Pr.7-02.
. Increase the acceleration time.
. Replace the AC drive with one that has
higher output capacity (next HP size).
Over-current during
deceleration:
. Short-circuit at motor
output.
. Deceleration time too
short.
. AC drive output
capacity is too small.
. Check for possible poor insulation at the
output line.
. Increase the deceleration time.
. Replace with the AC drive with one that
has a higher output capacity (next HP
size).
Over-current during
steady state operation:
. Short-circuit at motor
output.
. Sudden increase in
motor loading.
. AC drive output
capacity is too small.
. Check for possible poor insulation at the
output line.
. Check for possible motor stall.
. Replace the AC drive with one that has
higher output capacity (next HP size).
The external terminal
EF-GND goes from OF
to ON.
. When external terminal EF-GND is
closed, the output will be turned off.
(Under N.O. E.F.)
. Press RESET after fault has been
cleared.
Internal memory IC can
not be programmed.
. Return to the factory.
. Check the EEPROM on the control
board.