2-04 Reverse operation
inhibit
0: Enable reverse
1: Disable reverse
2: Disable forward
0
2-05 ACI (4 ~ 20mA)
input loss detection
0: Accel to 0Hz
1: Stop immediately, display EF
2: Run with the last freq.
0
2-06 Line Start Lockout
0: Enable
1: Disable
0
Group 3: Output Function Parameters
aramete
Functions Settings
Factor
Settin
3-00
esired freq. attained
.0 ~ 400 Hz 1.0
3-01
erminal count value
~ 999 0
3-02
reliminary count value
~ 999 0
3-03
ulti-function (relay
utput)
: not used
: AC drive operational
: Max. Output Freq. Attained
: Zero Speed
: Over Torque
: Base-Block (B.B.)
: Low Voltage Detection
: AC Drive Operation Mode
: Fault Indication
: Desired Freq. Attained
0: PLC Program Running
1: PLC Program Step Complete
2: PLC Program Complete
3: PLC Program Operation Pause
4: Terminal Count Value Attained
5: Preliminary Count Value Attained
6: Ready State Indicator
8
Group 4: Input Function Parameters
aramete
Functions Settings
Factor
settin
=
4-00
Potentiometer bia
freq.
0.0
350Hz
0.0
=
4-01
Potentiometer bias
polarity
0: positive bias 1: negative bias 0
=
4-02
Potentiometer fre
gain
1
200
&
100
4-03 Potentiometer 0: not used
reverse motion 1: reverse motion enable
0
enable 2: forward motion only