VFD-L Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Group 6: Protection Parameters
Parameter
Functions Settings
Factor
Settin
6-00
Over-Voltage Preventio
Level
0:disable
350~410V
390
6-01 Over-current Preventio
Level
0: disable
20~200%
170
6-02 Over-torque detection 0:disable
1:enable during constant speed
operation and continues until the
continuous limit is reached.
2:enabled during constant speed
operation and halted after detection.
3:enabled during accel and continues
before continuous output time limit is
reached.
4:enabled during accel and halted aft
over-torque detection.
0
6-03
Over-torque detectio
level
30 ~ 200% 150
6-04
Over-torque detectio
time
0.1 ~ 10.0 Sec 0.1
6-05
Electronic thermal
overload relay
0: Not used
1: Act with standard motor
2: Act with special motor
0
6-06
Electronic thermal
characteristic
30~600 Sec 60
6-07 Present fault record
6-08
Second most rece
fault record
6-09
Third most recent fault
record
6-10
Forth most recent fault
record
6-11
Fifth most recent fault
record
6-12
Sixth most recent fault
record
0: No fault occurred
1: oc (over current)
2: ov (over voltage)
3: oH (over heat)
4: oL (over load)
5: oL1 (electronic thermal)
6: EF (external fault)
7: Reserved
8: Reserved
9: ocA (current exceed during
acceleration)
10: ocd (current exceed during
deceleration)
11: ocn (current exceed during steady
state)
0