VFD-L Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Parameter
Functions Settings
Factor
Settin
8-14 Auto restart after fault 0~10 0
8-15 AVR function 0: AVR function enable
1: AVR function disable
2: AVR function disable when decel
2
8-16
ynamic braking voltage 350 ~ 450V 380
8-17
C braking lower boun
imit
0.0 ~ 400 Hz 0.0
Group 9: Communication Parameters
Parameter
Functions Settings
acto
Settin
=
9-00
Communication
address
1 ~ 247 1
=
9-01 Transmission speed
0: Baud rate 4800
1: Baud rate 9600
2: Baud rate 19200
1
=
9-02
Transmission fault
treatment
0: Warn and continue running
1: Warn and ramp to stop
2: Warn and coasting stop
3: No warn and keep running
0
=
9-03
Modbus
communication
watchdog timer
0: Disable
1~20: 1 ~ 20 Sec
0
ASCII
mode
0: 7,N,2
1: 7,E,1
2: 7,O,1
3: 8,N,2
4: 8,E,1
5: 8,O,1
=
9-04
Communication
protocol
RTU
mode
6: 8,N,2
7: 8,E,1
8: 8,O,1
0