xLogic SuperRelay User’s Manual
22
Note:
1. For ELC-18DC Series and ELC-12DC Series versions. That can receive analog
input. They can be set to analog input or switching input as either may be used in
the program. They will be recognized as analog inputs when the input terminal is
connected with an analog function block, and they will be recognized as
switching inputs when the input terminal is not connected with an analog
function block.
2. The analog inputs require DC 0V ~ +10V voltage signals. These are divided
equally in 0.02V increments. In programming, all the block parameters related to
the analog inputs are based on the minimum increment of 0.02V.
3. They can be recognized as switching input when the input voltage is more
than 10.0V and cannot be recognized as an analog input.
4. For the switching input off, when the switch status changes from 0 to 1,
the time of Status 1 must be greater than 50ms, and when the switch status
changes from 1 to 0, the time of Status 0 also must be greater than 50ms.
2. Connecting xLogic is shown as in the following figures:
* ELC-18DC and ELC-12DC Series inputs
* ELC-18AC Series and ELC-12AC inputs