8 SmartWire-DT
8.9 Programming
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 173
8.9.3.5 Profiles 4, 5, 6: inputs (status)
Input bytes are mapped as follows on SmartWire-DT.
Profiles 4, 5, and 6 correspond to profiles 1 to 3, but with an added status 
byte:
Profile 4 = Profile 1 (2 bytes) + DS7 status (1 byte)
Table 32: Profiles 4 to 6: input bytes
Byte Bit Designation Meaning
0 0 Not used
1 - 7 → section 8.9.3.2, “Inputs (status) profiles 1, 2, 
3”, page 161
1
2
3
4
+1
(Status 
DS7)
0 ERR Error present
0: no error
1: Error
1 WARN Warning present:
0: no warning
1: Warning
2 RDY Ready, switched on:
0: not switched on
1: switched on
3 RUN DS7 Run, power part active:
0: Stop (power section inactive)
1: Running (power section active)
4 TOR Top of ramp:
0: Top of start ramp not reached
1: Top of start ramp reached
5
1)
CL Current limit:
0: Current limit not reached
1: Current limit reached
6, 7 – Not used
1) Bit 5 will only be activated if parameter 681.0 is set to 1.