8 SmartWire-DT
8.9 Programming
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 175
8.9.3.7 Profiles 7, 8, 9: Inputs (status)
Input bytes are mapped as follows on SmartWire-DT.
Table 34: Profiles 7, 8, 9: Input bytes
Byte Bit Designation Meaning
0 → section 8.9.3.2, “Inputs (status) profiles 1, 2, 3”, page 161
1
2
3
4
+2 (Long) 0 RSO Ready to switch on: S2
0: Not ready for switching on
1: Ready for switching on
1 RDY Ready to operate; switched on: S3
0: not ready for operation
1: ready for operation
2 EN Operation (Enabled S4)
0: Stop
1: Operation
3 ERR Error present (Error)
0: no error
1: Error
4 C_Stop Free run-down, output de-energized (coast stop)
0: no free run-down
1: free run-down
5 Q_Stop Quick stop, shortest ramp
0: no quick stop
1: Quick stop
6 SOI Reclosing lockout (switching on inhibited: S1)
0: No switch-on inhibit
1: Switch-on inhibit
7 WARN Warning present:
0: no warning
1: Warning
8 RUN DS7 Run, power part active
0: Stop (power section inactive)
1: Running (power section active)
9 Ctl_Req Control requested to PLC
Is set if PNU 928.0 = 1.
0: Not ready for remote control
1: Ready for remote control
10 TOR Top of ramp:
0: Top of start ramp not reached
1: Top of start ramp reached
11
1)
CL Current limit:
0: Current limit not reached
1: Current limit reached
12 – Not used
+2 (Long) 0 - 15 Utilization (Int16) Load as a percentage (utilization %):
LB: Low Byte / HB: High Byte
0 - FFFF ≙
±200 % / 0x4000 ≙
±100 %
1) Bit 11 will only be activated if parameter 681.0 is set to 1.