8 SmartWire-DT
8.9 Programming
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 191
Profile-specific
927 0 rw ParameterAccess Unsigned16 Parameter level
Defines the parameter level. 
Changes are only possible if the 
DS7-SWD soft starter is stopped 
(state S1 or S2):
0: Local parameter access (control 
signal terminals and 
potentiometers)
1: Parameter access via network
2: Parameter access via network 
(except for potentiometer 
parameters), local access for 
potentiometers
0 - 2 2
928 0 rw ProcessDataAccess Unsigned16 Process data level:
Defines the process data level. 
Changes are only possible if the 
DS7-SWD soft starter is stopped 
(state S1 or S2):
0: Local control (control signal 
terminals and potentiometer)
1: Control via network
2: not used
3: not used
4: Control via network – automatic 
change to local control in the 
event of a loss of communications 
(PNU 928 = 0).
Switch back to network control as 
soon as communication is re-
established.
5: Dual mode. EN/Start-Stop must 
be applied simultaneously with 
the interface commands. They will 
only be valid if both are present.
Note:
In the case of firmware version 
V46 and lower, the unit will switch 
to local control automatically only 
if the soft starter was correctly 
started after being switched on.
0 - 5 4 (from 
version 
V46)
944 0 ro Fault Message 
Counter
Unsigned16 Fault counter
1)
0 - 65535
947 0 ro NewestFaultNumber Unsigned16 Fault Number
Fault numbers, listed 
chronologically
0 - 65535 0
947 1 ro Unsigned16 0 - 65535 0
947 2 ro Unsigned16 0 - 65535 0
947 3 ro Unsigned16 0 - 65535 0
947 4 ro Unsigned16 0 - 65535 0
947 5 ro Unsigned16 0 - 65535 0
947 6 ro Unsigned16 0 - 65535 0
947 7 ro OldestFaultNumber Unsigned16 0 - 65535 0
PNU
Index
PNU
Sub-
index
Access 
rights
Designation Data type Meaning Value range DS User 
setting