2.3.4
Con󰈌guration of the Analog Outputs
The Analog Outputs can be programmed to output for three di󰊍erent ranges of either »0‒
20mA«, »4‒20 mA«, or »0‒10 Volts«.
These outputs can be con󰊎gured by the user to represent the status of user-programmed
parameters that are available from the relay. The settings for this feature can be found in
the menu branch [Device Para / Analog Outputs].
The setting »Assignment« assigns a parameter to which the output will correlate.
Once the assignment has been made, the parameter »Range « selects the required
output type / range of the parameter that shall correlate to the analog output.
The user de󰊎nes a »Range min« and a »Range max«. The »Range min« determines the
value at which value the transmission starts. Likewise, the »Range max« value
determines the value that results in the end value of the transmission.
100%
0%
Range
Range of assigned value
Range min Range max
HPT_Z85
109www.eaton.comEMR-3MP0