EasyManua.ls Logo

Eaton EMR-3MP0 - Motor Start Recorder; Manage Start Records

Eaton EMR-3MP0
281 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.5 Motor Start Recorder
The Motor Start Recorder logs information during a motor start-up. These records are
stored in a fail-safe manner and the capacity allows for recording up to 5 start-ups. After 5
start-ups, every following start-up overwrites the recording of the oldest one (“First in First
out” principle).
Every recording consists of a summary of information and recorded analog trends.
However, the exact set of data is dependent on the ordered device variant. The summary
data can be accessed using PowerPort-E or via the front panel interface of the EMR-3MP0.
This feature provides information recorded at the time of each start of the motor such as:
Date of the motor start event
Record number
IA max RMS, IB max RMS, IC max RMS, IX max RMS – Maximum RMS phase current
of the respective phase
Unbalance max – Maximum current unbalance during the motor start-up
I avg – Average current of all three phases at the time of the start-to-run transition
Speed – The motor nominal speed (1 or 2)
Time (duration) values:
TSTI – The time that elapses from the start until the current value drops below
the set start-up threshold
TSTR – The time that elapses from the start until the motor is running, or – in
case of an incomplete start sequence – until trip
I2T used – Thermal capacity used, speci󰊎ed as percentage of the maximum thermal
capacity
Start success – This is set to 1 if the motor start has been successful (and equals 0
otherwise).
PowerPort-E allows for storing the summary information as text 󰊎les, or have them
printed out.
The analog trends can be viewed using the QualityManager software. Examples for
recorded analog trends are:
Phase current values
Current unbalance
Thermal capacity
Temperatures (in case an RTD box is 󰊎tted)
Manage Start Records
The start recorder data can be downloaded by means of PowerPort-E from the device.
206 www.eaton.com EMR-3MP0
5 Recorders
5.5 Motor Start Recorder

Table of Contents

Related product manuals