11.1.3
Electrical Tests
High Voltage Tests (IEC 60255-1)
High Frequency Interference Test
IEC 60255-22-1
IEC 60255-26
IEEE C37.90.1
IEC 61000-4-18
Within one circuit 1 kV / 2 s
Circuit to ground 2.5 kV / 2 s
class 3 Circuit to circuit 2.5 kV / 2 s
Insulation Voltage Test
IEC 60255-27
IEC 60255-5
EN 50178
All circuits to other circuits and
exposed conductive parts
2.5 kV (e󰊍.) / 50Hz, 1 min.
Except interfaces 1.5 kV DC, 1 min.
Voltage measuring input 3 kV (e󰊍.)/50 Hz, 1 min.
Impulse Voltage Test
IEC 60255-27
IEC 60255-5
5 kV / 0.5J, 1.2 / 50 µs
Insulation Resistance Test
IEC 60255-27
EN 50178
Within one circuit 500V DC , 5s
Circuit to circuit 500V DC , 5s
EMC Immunity Tests
Fast Transient Disturbance Immunity Test (Burst)
IEC 60255-22-4
IEC 60255-26
Power supply, mains inputs ±4 kV, 2.5 kHz
Other in- and outputs ±2 kV, 5 kHz
254 www.eaton.com EMR-3MP0
11 Appendix
11.1 Standards