Fast Transient Disturbance Immunity Test (Burst)
IEC 61000-4-4
class 4
Surge Immunity Test (Surge)
IEC 60255-22-5
IEC 60255-26
IEC 61000-4-5
class 4
Within one circuit 2 kV
Circuit to ground 4 kV
class 3 Communication cables to ground 2 kV
Electrical Discharge Immunity Test (ESD)
IEC 60255-22-2
IEC 60255-26
IEC 61000-4-2
class 3
Air discharge 8 kV
Contact discharge 6 kV
Radiated Radio Frequency Electromagnetic Field Immunity Test
IEC 60255-22-3
IEC 60255-26
IEC 61000-4-3
26 MHz – 80 MHz 10 V/m
80 MHz – 1 GHz 35 V/m
1 GHz – 3 GHz 10 V/m
Immunity to Conducted Disturbances Induced by Radio Frequency Fields
IEC 61000-4-6
IEC 60255-26
class 3
150kHz - 80MHz 10 V
Power Frequency Magnetic Field Immunity Test
IEC 61000-4-8
IEC 60255-26
continuous 30 A/m
3 sec 300 A/m
255www.eaton.comEMR-3MP0
11 Appendix
11.1 Standards