Page #244 background image
10.1 Tolerances / Speci󰈌cations
10.1.1
Speci󰈌cations of the Real Time Clock
Resolution: 1 ms
Tolerance: <1 minute / month (+20°C [68°F])
<±1ms if synchronized via IRIG-B
Time Synchronization Tolerances
The di󰊍erent protocols for time synchronisation vary in their accuracy:
Used Protocol Time drift over one
month
Deviation to time generator
Without time
synchronization
<1 min (+20°C) Time drifts
IRIG-B Dependent on the time drift
of the time generator
<±1 ms
SNTP Dependent on the time drift
of the time generator
<±1 ms, if network connection is
GOOD (see operation status of SNTP)
Modbus TCP Dependent on the time drift
of the time generator
Dependent on the network load
Modbus RTU Dependent on the time drift
of the time generator
<±1 ms
DNP3 TCP Dependent on the time drift
of the time generator
Dependent on the network load
DNP3 UDP Dependent on the time drift
of the time generator
Dependent on the network load
DNP3 RTU Dependent on the time drift
of the time generator
<±1 ms
Note that the availability of the protocols depends on the ordered variant of the
EMR-3MP0 (see ╚═▷ “Catalog Codes for the EMR-3MP0”).
244 www.eaton.com EMR-3MP0
10 Technical Data EMR-3MP0
10.1 Tolerances / Speci󰊎cations

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EMR-3MP0 and is the answer not in the manual?

Eaton EMR-3MP0 Specifications

General IconGeneral
BrandEaton
ModelEMR-3MP0
CategoryRelays
LanguageEnglish

Related product manuals