EasyManua.ls Logo

Eaton EMR-3MP0 - Trip Bypass Functionality; Trip Bypass Commissioning Example

Eaton EMR-3MP0
281 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.15.2
Trip Bypass Functionality
Breaker Failure Protection for devices that o󰃠er current measurement
Trip Bypass
CBF_E91
2
51
14
Please Refer to Diagram: Blockings
(Element is not deactivated and no active blocking signals.)
Trip Bypass . Trip
Φ
IA
IB
IC
Trip Bypass . Pickup
Trip Bypass . Waiting for Trigger
1 s
0
0.1In
OR
Prot . Trip
4.15.3
Trip Bypass Commissioning Example
Object to Be Tested:
Test of the »Trip Bypass« module.
Necessary Means:
Current source;
Ammeter; and
Timer.
NOTICE!
When testing, the applied test current must always be higher than the device-internal
threshold 0.1⋅In.
If the test current falls below the threshold while the breaker is in the O󰊍” position, no
pickup is generated.
Procedure (Single-Phase):
For testing the tripping time of the »Trip Bypass« module, a test current has to be higher
than the threshold value of one of a current protection module. The »Trip Bypass« trip
delay can be measured from the time when General Trip signal »Prot . Trip« becomes
active, to the time when the »Trip Bypass . Trip« signal becomes active.
To avoid wiring errors, make sure the breaker in the upstream system switches o󰊍.
The time, measured by the timer, should be in line with the speci󰊎ed tolerances.
Successful Test Result:
191www.eaton.comEMR-3MP0
4 Protective Elements
4.15 Trip Bypass [50BF/62BF]

Table of Contents

Related product manuals