10.1.3.3 Motor Protection
Motor Protection: Accuracy
Stop Declaration
Time period current must drop below STPC
<50 ms
±1.5% of the setting value or 1% In
Anti Backspin
Blocking time to allow for back spin
±1 s
TBS Timer
Time between repeated starts.
±1 s
Reset Starts Per Hour
Reset starts per hours timer from oldest
start event.
±1 minute
Jam-Stall Protection: 50J Accuracy
Pickup ±1.5% of the setting value or 1% In
Dropout Ratio ±97% or 0.5% In
t DEFT
±1% or ±10 ms
Operating Time
Starting from I higher than 1.1 x I>
<35 ms
Disengaging Time <45 ms
248 www.eaton.com EMR-3MP0
10 Technical Data EMR-3MP0
10.1 Tolerances / Specications