Under Load Protection: 37[x] Accuracy
Threshold ±1.5% of the setting value or 1% In
Dropout Ratio 103% or 0.5% In
t DEFT
±1% or ±10 ms
Operating Time
Starting from I lower than 0.8 x setting
value
<35 ms
Disengaging Time
Starting from I ≥ 2 times setting value
<24 ms
Mechanical Load Shedding: MLS Accuracy
Pickup Threshold ±1.5% of the setting value or 1% In
Pickup Delay DEFT
±1% or ±10 ms
Dropout Threshold ±1.5% of the setting value or 1% In
Dropout Delay DEFT
±1% or ±10 ms
Start Delay Timers Accuracy
Start Delay (common timers) ±1% or ±10 ms
Operating Times
for IOC, GOC, JAM <35 ms
for Underload, Generic 1-5 <60 ms
249www.eaton.comEMR-3MP0
10 Technical Data EMR-3MP0
10.1 Tolerances / Specications