EasyManua.ls Logo

Eaton EMR-3MP0 - Start Control

Eaton EMR-3MP0
281 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.2.4
Start Control
I
»TRNC«
30%  FLA
t
MotorStart_Z02
»TRN Criteria« = “TRN I”:
Stop Start Run
»TRN Criteria« = “TRN T or I”:
Stop Start Run
»TRN Criteria« = “TRN TIME”:
»TRNT«
RunStop Start
RunStop Start
»TRN Criteria« = “TRN T and I”:
The Start Control Module drawing shows an example of how the EMR-3MP0 reacts to a
normal operating-cycle current pro󰊎le. Initially, the motor is stopped and the current is
zero. As long as the EMR-3MP0 is not in a trip state, it permits contactor energization by
closing its trip contact in series with the contactor. The contactor is energized by the
operator or process control system through a normal two-wire or three-wire motor control
scheme, external to the protective device.
The EMR-3MP0 declares a motor start when it senses a motor current that exceeds 30%
of the FLA setting, [System Para] »FLA«.
Meanwhile, the transition timer, [Protection Para / MStart / Start Control] »TRNT«, begins
to run.
The EMR-3MP0 also monitors the large starting current, noting when the current falls
below the transition level [Protection Para / MStart / Start Control] »TRNC«.
143www.eaton.comEMR-3MP0
4 Protective Elements
4.2 Motor Starting and Control Module

Table of Contents

Related product manuals