4.2.3
Motor Start / Transition Trips
The motor is tripped during the start phase, in case that:
The Start Control detects an unsuccessful start. (See ╚═▷ “Start Control”.)
There is an Incomplete Start Sequence. The device detects via an digital input that
the external process is not properly started.
If a reverse direction is detected but reversing is not allowed. (See ╚═▷ “Reversing or
Non-Reversing Starter.)
If case of a Zero Speed Switch trip.
141www.eaton.comEMR-3MP0
4 Protective Elements
4.2 Motor Starting and Control Module