2.3.3
Relay Output Con󰈌guration
The State of the Relay Outputs can be checked within the menu: [Operation / Status
Display / Name of the assembly group (e. g. RO-3 X)]
The Relay Outputs can be con󰊎gured within the menu: [Device Para / Relay Outputs /
Name of the assembly group (e. g. RO-3 X)]
Set the following parameters for each of the relay output contacts.
»Assigned signals«: The parameters »Assignment 1« to »Assignment 7« can be used
to assign up to 7 trigger signals (OR-connected).
The states of the module outputs and the signals (e.g. states of protective functions) can
be assigned to the relay output contacts. The relay output contacts are “dry-
type“ contacts.
By the »Operating Mode« it can be determined whether the relay output works in
Normally »De-Energized« or »Normally Energized« principle.
NOTICE!
The »System OK Relay« (watchdog) cannot be con󰊎gured.
108 www.eaton.com EMR-3MP0
2 Hardware
2.3 Input, Output and LED Settings