1.5 Resets
Collective Resets of Latched Signals
Collective Resets
LEDs Relay
Outputs
SCADA Trips LEDs +
Binary
Output
Relays +
SCADA +
Trips
Via
PowerPort-E
or at the panel
all … can be
reset.
At the panel,
the menu
[Operation /
Reset] can
directly be
accessed via
the »C« key
All LEDs at
once:
Where?
[Operation /
Reset]
All Binary
Output Relays
at once:
Where?
[Operation /
Reset]
All SCADA
signals at
once:
Where?
[Operation /
Reset]
All pending
trips at once:
Where?
[Operation /
Reset]
All at once:
Where?
[Operation /
Reset]
External
Reset*:
Via a signal
from the
assignment list
(e. g. a digital
Input) all... can
be reset.
All LEDs at
once:
Where? Within
the [Device
Para / Reset]
menu
All Binary
Output Relays
at once:
Where? Within
the menu
[Device Para /
Reset]
All SCADA
signals at
once:
Where? Within
the menu
[Device Para /
Reset]
All pending trip
commands at
once:
Where? Within
the menu
[Device Para /
Reset]
All at once:
Where? Within
the [Device
Para / Reset]
menu
See also ╚═▷ “1.5 External Reset” below.
Manual Reset
It is possible to reset LEDs, SCADA, Relay Outputs and pending trips by pressing the »Ack/
Rst« at the panel.
There are two methods available with pressing the »Ack/Rst« key:
Short keypress: With intermediate selection step: After the »Ack/Rst« key has been
pressed (for a short time), you select the items to be reset (LEDs, SCADA, Relay
Outputs, trips) via the Softkeys. After this, you press the Softkey with the »Wrench-
Symbol«.
50 www.eaton.com EMR-3MP0
1 EMR‑3MP0 Motor Protection Relay
1.5 Resets