Modbus TCP
NOTICE!
Establishing a connection via TCP/IP to the device is only possible if the device is
equipped with an Ethernet Interface (RJ45).
Contact your IT administrator in order to establish the network connection.
Part 1: Setting the TCP/IP Parameters
Call up [Device Para / TCP/IP / TCP/IP con󰊎g] at the HMI (panel) and set the following
parameters:
TCP/IP address;
Subnet mask; and
Gateway.
Part 2: Con󰅡guration of the Devices
Call up »Device parameter/Modbus« and set the following communication parameters.
Setting a unit identi󰊎er is only necessary if a TCP network should be coupled to a
RTU network.
If a di󰊍erent port than the default port 502 should be used, please proceed as
follows:
Choose “Private” within the TCP-Port-Con󰊎guration.
Set the port number.
Set the maximum acceptable time out for “no communication”. If this time has
expired without any communication, the device concludes a failure has occurred
within the master system.
Allow or disallow the blocking of SCADA commands.
Part 3: Hardware Connection
There is a RJ45 interface at the rear side of the device for the hardware connection
to the control system.
Establish the connection to the device by means of a proper Ethernet cable.
115www.eaton.comEMR-3MP0
3 Communication Protocols
3.3 Modbus®