Then con󰊎gure the switching of daylight saving time.
Then, in the menu branch [Device Para / Time / TimeSync / TimeSync]:
Set the parameter »TimeSync« to the used time synchronization protocol (e.g. “IRIG-
B”).
Set the parameters of the synchronization protocol (refer to the according chapter).
Time Synchronization with local time:
Should the time synchronization however be done using local time, then please leave the
timezone to “UTC+0 London” and do not use switching of daylight saving time.
NOTICE!
The synchronization of the relay's system time is exclusively done by the synchronization
protocol selected in the menu [Device Para / Time / TimeSync / TimeSync].
Without Time Synchronization:
To achieve that the device shows the current local time, the timezone and the change to
Daylight Saving Time can be con󰊎gured.
Please carry out the following setting steps:
In the menu branch [Device Para / Time / TimeSync / TimeSync], set the
parameter »TimeSync« to “-”.
Then, in the menu branch [Device Para / Time / Timezone], set the parameter »Time
Zones« to your local timezone.
Then con󰊎gure the switching of daylight saving time.
Set date and time at [Device Para / Time] »Date and Time«.
128 www.eaton.com EMR-3MP0
3 Communication Protocols
3.7 Time Synchronization