RTD . Any Group
RTD_E02
All pickups, timeout alarms and trips of the groups are connected by an OR-gate in order to generate a group pickup, a group timeout alarm or and group trip.
RTD . Alarm WD Group
RTD . Alarm Any Group
OR
RTD . Alarm Aux Group
RTD . TimeoutAlmWDGrp
RTD . TimeoutAlmAnyGrp
OR
RTD . TimeoutAlmAuxGrp
RTD . Trip WD Group
RTD . Trip Any Group
OR
RTD . Trip Aux Group
RTD . Alarm MB Group
RTD . Alarm LB Group
RTD . TimeoutAlmMBGrp
RTD . TimeoutAlmLBGrp
RTD . Trip MB Group
RTD . Trip LB Group
Collective Timeout Alarm Signal
All RTD sensor timeout alarms and all group timeouts are OR-connected.
RTD . Timeout Alarm
RTD_E94
All timeout alarms are OR connected to a collective alarm.
RTD . TimeoutAlmWDGrp
RTD . Alarm
OR
RTD . TimeoutAlmAuxGrp
Collective Trip Signal
All RTD group trip signals are OR-connected, resulting in the collective trip signal »RTD .
Trip«.
RTD . Trip
RTD_E95
All trips are OR connected to a collective trip signal.
14
RTD . Trip
15
RTD . Trip WD Group
OR
RTD . Trip Aux Group
RTD . Trip MB Group
RTD . Trip LB Group
184 www.eaton.com EMR-3MP0
4 Protective Elements
4.13 26/38/49 – RTD Protection Module