Forcing an entire group takes precedence over forcing a single relay output contact!
NOTICE!
A relay output contact WILL NOT follow a force command as long as it is disarmed at the
same time.
NOTICE!
A relay output contact WILL follow a force command:
• If it is not disarmed; and
• If the Direct Command is applied to the relay(s).
Keep in mind, that forcing all relay output contacts (of the same assembly group) takes
precedence over the force command of a single relay output contact.
227www.eaton.comEMR-3MP0
8 Commissioning
8.3 Service and Commissioning Support