Manual start, stop by external signal:
Force Post: As soon as this signal becomes true, the Fault Simulation is forced to switch
into the Post Failure mode.
• Set [Service / Test Mode (Prot inhibit) / WARNING! Cont? / Sgen / Process] »Ex
ForcePost« to the required signal.
• Press/Call the Direct Control [Service / Test Mode (Prot inhibit) / WARNING! Cont? /
Sgen / Process] »Start Simulation«.
Manual start, manual stop:
As soon as the stop command is given, the Fault Simulation is terminated and the
EMR-3MP0 changes back to normal operation.
• Start: as described above.
•
Stop: Press/Call the Direct Control [Service / Test Mode (Prot inhibit) / WARNING!
Cont? / Sgen / Process] »Stop Simulation«.
Start by external signal:
The start of the Fault Simulator is triggered by the assigned external signal (unless it is
blocked).
(Moreover, as already said above, ╚═▷ Chapter 8.3.6, the use of the Fault Simulator
generally requires that no phase current exceeds 0.1 ⋅ In.)
• Set [Service / Test Mode (Prot inhibit) / WARNING! Cont? / Sgen / Process] »Ex Start
Simulation« to the required signal.
234 www.eaton.com EMR-3MP0
8 Commissioning
8.3 Service and Commissioning Support