Mechanical Mounting of the Unit of the Cabinet Door
With each maintenance or yearly:
• Check the torque (1.7 Nm [15 in⋅lb]) related to the specication of the Installation
chapter, ╚═▷ “Dimension Drawings”.
Torque of all Cable Connections
With each maintenance or yearly:
• Check the torque related to the specication of the Installation chapter (╚═▷
“EMR-3MP0 – Installation and Wiring”) which describes the hardware modules.
We recommend to execute a protection test after each 4 years period. This period can be
extended to 6 years if a function test is executed at least every 3 years.
236 www.eaton.com EMR-3MP0
9 Servicing and Maintenance