HPT_ZC1
IRIG-B-
RO1 NO
IRIG-B+
RO2 NO
RO3 CMN
RO3 NO
RO4 CMN
RO4 NO
RO3 NC
RO4 NC
1
3
2
4
5
6
7
8910
11
12
13
14
15
16
17
18
PE
N.C.
N.C.
N.C.
+
Analog Output
Fig. 14: RO-3AI - Pin Assignment
For details on the Analog Output please refer to the Technical Data, ╚═▷ “Technical Data
EMR-3MP0”.
Relay Outputs
The Relay Outputs are potential-free contacts.
The assignment of the Relay Outputs is described in ╚═▷ “Relay Output Con󰊎guration.
Check the “EMR-3MP0 Reference Manual” (separate document) for a list of signals that
can be assigned.
CAUTION!
Please carefully consider the current carrying capacity of the Relay Outputs. Please refer
to the Technical Data (╚═▷ “Technical Data EMR-3MP0”).
Selfsupervision Contact
The Selfsupervision Contact contact (“SC”) cannot be con󰊎gured. It is a changeover (Form
C”) contact that picks up when the device is free from internal faults. While the device is
booting up, the “SC” relay remains dropped-o󰊍 (unenergized). As soon as the system is
properly started (and protection is active), it picks up and the assigned LED is activated
accordingly (please refer to the Self Supervision chapter, ╚═▷ “Self-Supervision).
78 www.eaton.com EMR-3MP0
2 Hardware
2.2 EMR-3MP0 – Installation and Wiring