www.eaton.com IM02601001E C-3
Modbus Register Maps
Parameter Name Display Name Base Address
(0-based)
Discrete Units Type Size
(bytes)
Is Time-
stamp?
Bit
Offset
Swap
Bytes
Swap
Words
Divider Multiplier Date
Spec
Alarm On
False
Writable Possible Values
mVarB/Value Reactive Power Phase B 6130 No volt-
amperes-
reactive
FLOAT 4 No No No No
mVarC/Value Reactive Power Phase C 6132 No volt-
amperes-
reactive
FLOAT 4 No No No No
mVARtotal/Value Reactive Power 6134 No volt-
amperes-
reactive
FLOAT 4 No No No No
mPFapparentA/Value PF App Phase A 6212 No power-
factor
FLOAT 4 No No No No
mPFapparentB/Value PF App Phase B 6214 No power-
factor
FLOAT 4 No No No No
mPFapparentC/Value PF App Phase C 6216 No power-
factor
FLOAT 4 No No No No
mPFapparentTotal/Value PF Apparent 6220 No power-
factor
FLOAT 4 No No No No
mPFapparentTotal5MinIntAvg/Value PF App Total Interval Avg 6316 No power-
factor
FLOAT 4 No No No No
mForwardEnergy/Value Forward Real Energy 7004 No watt-hours FLOAT 4 No No No
No
mReverseEnergy/Value Reverse Real Energy 7006 No watt-hours FLOAT 4 No No No No
mNetEnergy/Value Net Real Energy 7008 No watt-hours FLOAT 4 No No No No
mLeadingVARh/Value Leading Reactive Energy 7010 No volt-
ampere-
reactive-
hours
FLOAT 4 No No No No
mLaggingVARh/Value Lagging Reactive Energy 7012 No volt-
ampere-
reactive-
hours
FLOAT 4 No No No No
mNetVARh/Value Net Reactive Energy 7014 No volt-
ampere-
reactive-
hours
FLOAT 4 No No No No
mVAh/Value Apparent Energy 7016 No volt-am-
pere-hours
FLOAT 4 No No No No
mDemandSumWatts/Value Demand Sum Watts 7025 No watts FLOAT 4 No No No No
mDemandNetWatts/Value Demand Net Watts 7027 No watts FLOAT 4 No No No No
mDemandSumVARs/Value Demand Sum VARs 7031 No volt-
amperes-
reactive
FLOAT 4 No No No No
mDemandNetVARs/Value Demand Net VARs 7033 No volt-
amperes-
reactive
FLOAT 4 No No No No
mTimeLastDemand/Value Time Last Demand Window 7037 No no-units DATE 6 No
No No ymd-
HMS
No
mDemandType/Value Demand Type 7165 No no-units UINT 2 No No No Yes Fixed(1); Sliding(2); Sync(3);
Unknown(4)
mTotalDemandInterval/Value Demand Interval 7166 No minutes FLOAT 4 No No No No 5; 10; 15; 20; 30; 45; 60
mDemandSubinterval/Value Demand Subinterval 7168 No minutes FLOAT 4 No No No Yes 5; 15; 30; 60
mIntDemandForwardWatts/Value Interval Demand Forward Watts 7170 No watts FLOAT 4 No No No No
mIntDemandReverseWatts/Value Interval Demand Reverse Watts 7172 No watts FLOAT 4 No No No No