C-4 IM02601001E www.eaton.com
Modbus Register Maps
Parameter Name Display Name Base Address
(0-based)
Discrete Units Type Size
(bytes)
Is Time-
stamp?
Bit
Offset
Swap
Bytes
Swap
Words
Divider Multiplier Date
Spec
Alarm On
False
Writable Possible Values
mIntDemandLaggingVARs/Value Interval Demand Lagging VARs 7174 No volt-
amperes-
reactive
FLOAT 4 No No No No
mIntDemandLeadingVARs/Value Interval Demand Leading VARs 7176 No volt-
amperes-
reactive
FLOAT 4 No No No No
mIntDemandVAs/Value Interval Demand VAs 7178 No volt-
amperes
FLOAT 4 No No No No
mDemandForwardWatts/Value Demand Forward Watts 7220 No watts FLOAT 4 No No No No
mPeakDemandForwardWatts/Value Peak Demand Forward Watts 7222 No watts FLOAT 4 No No No No
mTimeDatePeakDemandForward-
Watts/Value
Peak Demand Forward Watts Time 7224 No DATE 6 No No No ymd-
HMS
No
mDemandReverseWatts/Value Demand Reverse Watts 7262 No watts FLOAT 4 No No No No
mPeakDemandReverseWatts/Value Peak Demand Reverse Watts 7264 No watts FLOAT 4 No No No No
mTimeDatePeakDemandReverse-
Watts/Value
Peak Demand Reverse Watts Time 7266 No no-units DATE 6 No No No
ymd-
HMS
No
mDemandLaggingVARs/Value Demand Lagging VARs 7303 No volt-
amperes-
reactive
FLOAT 4 No No No No
mPeakDemandLaggingVARs/Value Peak Demand Lagging VARs 7305 No volt-
amperes-
reactive
FLOAT 4 No No No No
mTimeDatePeakDemandLagging-
VARs/Value
Peak Demand Lagging VARs Time 7307 No no-units DATE 6 No No No ymd-
HMS
No
mDemandLeadingVARs/Value Demand Leading VARs 7345 No volt-
amperes-
reactive
FLOAT 4 No No No No
mPeakDemandLeadingVARs/Value Peak Demand Leading VARs 7347 No volt-
amperes-
reactive
FLOAT 4 No No No No
mTimeDatePeakDemandLeading-
VARs/Value
Peak Demand Leading VARs Time 7349 No no-units DATE 6 No No No ymd-
HMS
No
mDemandVAs/Value Demand VAs 7387 No volt-
amperes
FLOAT 4 No No No No
mPeakDemandVAs/Value Peak Demand VAs 7389 No volt-
amperes
FLOAT 4 No No No No
mTimeDatePeakDemandVAs/Value Peak Demand VAs Time 7391 No no-units DATE 6 No No No ymd-
HMS
No
mDemandAmpsAvg/Value Demand Current (3 Phase Avg) 7429 No amperes FLOAT 4 No
No No No
mPeakDemandAmpsAvg/Value Peak Demand Amps Avg 7431 No amperes FLOAT 4 No No No No
mTotalVARh/Value Total Reactive Energy 7628 No volt-
ampere-
reactive-
hours
FLOAT 4 No No No No
mTotalEnergy/Value Total Real Energy 7679 No watt-hours FLOAT 4 No No No No
mPeakDemandSumWatts/Value Peak Demand Sum Watts 7683 No watts FLOAT 4 No No No No
mPeakDemandNetWatts/Value Peak Demand Net Watts 7688 No watts FLOAT 4 No No No No
mPeakDemandSumVARs/Value Peak Demand Sum VARs 7693 No volt-
amperes-
reactive
FLOAT 4 No No No No
mPeakDemandNetVARs/Value Peak Demand Net VARs 7698 No volt-
amperes-
reactive
FLOAT 4 No No No No