C-32 IM02601001E www.eaton.com
Modbus Register Maps
07EB - 07EC 2028 - 2029 Positive VARs, Phase A, Average FLOAT -9999 M to +9999
M
VARs
2
07ED - 07EE 2030 - 2031 Positive VARs, Phase B, Average FLOAT -9999 M to +9999
M
VARs
2
07EF - 07F0 2032 - 2033 Positive VARs, Phase C, Average FLOAT -9999 M to +9999
M
VARs
2
07F1 - 07F2 2034 - 2035 Negative Watts, Phase A, Average FLOAT -9999 M to +9999
M
watts
2
07F3 - 07F4 2036 - 2037 Negative Watts, Phase B, Average FLOAT -9999 M to +9999
M
watts
2
07F5 - 07F6 2038 - 2039 Negative Watts, Phase C, Average FLOAT -9999 M to +9999
M
watts
2
07F7 - 07F8 2040 - 2041 Negative VARs, Phase A, Average FLOAT -9999 M to +9999
M
VARs
2
07F9 - 07FA 2042 - 2043 Negative VARs, Phase B, Average FLOAT -9999 M to +9999
M
VARs
2
07FB - 07FC 2044 - 2045 Negative VARs, Phase C, Average FLOAT -9999 M to +9999
M
VARs
2
07FD - 07FE 2046 - 2047 VAs, Phase A, Average FLOAT -9999 M to +9999
M
VAs
2
07FF - 0800 2048 - 2049 VAs, Phase B, Average FLOAT -9999 M to +9999
M
VAs
2
0801 - 0802 2050 - 2051 VAs, Phase C, Average FLOAT -9999 M to +9999
M
VAs
2
0803 - 0804 2052 - 2053 Positive PF, Phase A, Average FLOAT -1.00 to +1.00 none
2
0805 - 0806 2054 - 2055 Positive PF, Phase B, Average FLOAT -1.00 to +1.00 none
2
0807 - 0808 2056 - 2057 Positive PF, Phase C, Average FLOAT -1.00 to +1.00 none
2
0809 - 080A 2058 - 2059 Negative PF, Phase A, Average FLOAT -1.00 to +1.00 none
2
080B - 080C 2060 - 2061 Negative PF, Phase B, Average FLOAT -1.00 to +1.00 none
2
080D - 080E 2062 - 2063 Negative PF, Phase C, Average FLOAT -1.00 to +1.00 none
2
Block Size: 64
Phase Angle Block
read-only
1003
-
1003 4100
-
4100 Phase A Current SINT16 -1800 to +1800 0.1 degree
1
1004 - 1004 4101 - 4101 Phase B Current SINT16 -1800 to +1800 0.1 degree
1
1005 - 1005 4102 - 4102 Phase C Current SINT16 -1800 to +1800 0.1 degree
1
1006 - 1006 4103 - 4103 Angle, Volts A-B SINT16 -1800 to +1800 0.1 degree
1
1007 - 1007 4104 - 4104 Angle, Volts B-C SINT16 -1800 to +1800 0.1 degree
1
1008 - 1008 4105 - 4105 Angle, Volts C-A SINT16 -1800 to +1800 0.1 degree
1
Block Size: 6
Status Block
read-only
1193
-
1193 4500
-
4500 Port ID UINT16 1 to 4 none Identifies which COM
port a master is con-
nected to: 2 for COM2,
etc. See chapter 5 for
COM port assignments.
1