EasyManua.ls Logo

Eaton Pow-R-Line SPX0361126 - Page 205

Eaton Pow-R-Line SPX0361126
584 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.eaton.com IM02601001E C-33
Modbus Register Maps
1194 - 1194 4501 - 4501 Meter Status UINT16 bit-mapped mmmpch-- -ffeeccc mmm = measurement
state (0=off, 1=running
normally, 2=limp mode,
3=warmup, 6&7=boot,
others unused) See
note 16.
pch = NVMEM block
OK flags (p=profile,
c=calibration,
h=header), flag is 1
if OK
ff = flash state
(0=initializing, 1=logging
disabled by Vswitch,
3=logging)
ee = edit state
(0=startup, 1=normal,
2=privileged command
session, 3=profile
update mode)
ccc = port enabled
for edit(0=none,
1-4=COM1-COM4,
7=front panel)
1
1195 - 1195 4502 - 4502 Limits Status UINT16 bit-mapped 87654321 87654321 High byte is setpt 1,
0=in, 1=out
low byte is setpt 2,
0=in, 1=out
see notes 11, 12, 17
1
1196 - 1197 4503 - 4504 Time Since Reset UINT32 0 to 4294967294 4 msec Wraps around after max
count.
2
1198 - 119A 4505 - 4507 Meter On Time TSTAMP 1Jan2000 -
31Dec2099
1 sec
3
119B - 119D 4508 - 4510 Current Date and Time TSTAMP 1Jan2000 -
31Dec2099
1 sec
3
119E - 119E 4511 - 4511 Reserved
Reserved 1
119F - 119F 4512 - 4512 Current Day of Week UINT16 1 to 7 1 day 1=Sun, 2=Mon, etc. 1
Block Size: 13
THD Block
13
read-only
176F
-
176F 6000
-
6000 Volts A-N, %THD UINT16 0 to 10000 0.01%
1
1770 - 1770 6001 - 6001 Volts B-N, %THD UINT16 0 to 10000 0.01%
1
1771 - 1771 6002 - 6002 Volts C-N, %THD UINT16 0 to 10000 0.01%
1
1772 - 1772 6003 - 6003 Amps A, %THD UINT16 0 to 10000 0.01%
1
1773 - 1773 6004 - 6004 Amps B, %THD UINT16 0 to 10000 0.01%
1
1774 - 1774 6005 - 6005 Amps C, %THD UINT16 0 to 10000 0.01%
1

Table of Contents