EasyManua.ls Logo

Eaton Pow-R-Line SPX0361126 - Page 206

Eaton Pow-R-Line SPX0361126
584 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C-34 IM02601001E www.eaton.com
Modbus Register Maps
1775 - 179C 6006 - 6045 Phase A Voltage harmonic magnitudes UINT16 0 to 10000 0.01% In each group of 40
registers, the first
register represents the
fundamental frequency
or first harmonic, the
second represents
the second harmonic,
and so on up to the
40th register which
represents the 40th
harmonic.
Harmonic magnitudes
are given as % of the
fundamental magnitude.
Thus the first register
in each group of 40
will typically be 9999.
A reading of 10000
indicates invalid.
40
179D - 17C4 6046 - 6085 Phase A Voltage harmonic phases SINT16 -1800 to +1800 0.1 degree 40
17C5 - 17EC 6086 - 6125 Phase A Current harmonic magnitudes UINT16 0 to 10000 0.01% 40
17ED - 1814 6126 - 6165 Phase A Current harmonic phases SINT16 -1800 to +1800 0.1 degree 40
1815 - 183C 6166 - 6205 Phase B Voltage harmonic magnitudes UINT16 0 to 10000 0.01% 40
183D - 1864 6206 - 6245 Phase B Voltage harmonic phases SINT16 -1800 to +1800 0.1 degree 40
1865 - 188C 6246 - 6285 Phase B Current harmonic magnitudes UINT16 0 to 10000 0.01% 40
188D - 18B4 6286 - 6325 Phase B Current harmonic phases SINT16 -1800 to +1800 0.1 degree 40
18B5 - 18DC 6326 - 6365 Phase C Voltage harmonic magnitudes UINT16 0 to 10000 0.01% 40
18DD - 1904 6366 - 6405 Phase C Voltage harmonic phases SINT16 -1800 to +1800 0.1 degree 40
1905 - 192C 6406
- 6445 Phase C Current harmonic magnitudes UINT16 0 to 10000 0.01% 40
192D - 1954 6446 - 6485 Phase C Current harmonic phases SINT16 -1800 to +1800 0.1 degree
40
1955 - 1955 6486 - 6486 Wave Scope scale factor for channel Va UINT16 0 to 32767
Convert individual
samples to volts or
amps:
V or A = (sample * scale
factor) / 1,000,000
Samples update in
conjunction with THD
and harmonics; samples
not available (all zeroes)
if THD not available.
1
1956 - 1956 6487 - 6487 Wave Scope scale factors for channel Ib UINT16 0 to 32767
1
1957 - 1958 6488 - 6489 Wave Scope scale factors for channels Vb
and Ib
UINT16 0 to 32767
2
1959 - 195A 6490 - 6491 Wave Scope scale factors for channels Vc
and Ic
UINT16 0 to 32767
2
195B - 199A 6492 - 6555 Wave Scope samples for channel Va SINT16 -32768 to +32767
64
199B - 19DA 6556 - 6619 Wave Scope samples for channel Vb SINT16 -32768 to +32767
64
19DB - 1A1A 6620 - 6683 Wave Scope samples for channel Vc SINT16 -32768 to +32767
64
1A1B - 1A5A 6684 - 6747 Wave Scope samples for channel Ia SINT16 -32768 to +32767
64
1A5B - 1A9A 6748 - 6811 Wave Scope samples for channel Ib SINT16 -32768 to +32767
64
1A9B - 1ADA 6812 - 6875 Wave Scope samples for channel Ic SINT16 -32768 to +32767
64
Block Size: 876

Minimum


1F3F - 1F40 8000 - 8001 Volts A-N, Minimum FLOAT 0 to 9999 M volts 2
1F41 - 1F42 8002 - 8003 Volts B-N, Minimum FLOAT 0 to 9999 M volts 2
1F43 - 1F44 8004 - 8005 Volts C-N, Minimum FLOAT 0 to 9999 M volts 2
1F45 - 1F46 8006 - 8007 Volts A-B, Minimum FLOAT 0 to 9999 M volts 2
1F47 - 1F48 8008 - 8009 Volts B-C, Minimum FLOAT 0 to 9999 M volts 2
1F49 - 1F4A 8010 - 8011 Volts C-A, Minimum FLOAT 0 to 9999 M volts 2
1F4B - 1F4C 8012 - 8013 Amps A, Minimum Avg Demand FLOAT 0 to 9999 M amps 2
1F4D - 1F4E 8014 - 8015 Amps B, Minimum Avg Demand FLOAT 0 to 9999 M amps 2
1F4F - 1F50 8016 - 8017 Amps C, Minimum Avg Demand FLOAT 0 to 9999 M amps 2

Table of Contents