www.eaton.com IM02601001E C-53
Modbus Register Maps
753E - 753E 30015 - 30015 User Settings Flags UINT16 bit-mapped ---g--nn srpdywf- g = enable alternate full
scale bar graph current
(1=on, 0=off)
nn = number of phases
for voltage & current
screens (3=ABC, 2=AB,
1=A, 0=ABC)
s = scroll (1=on, 0=off)
r = password for reset in
use (1=on, 0=off)
p = password for
configuration in use
(1=on, 0=off)
d = daylight saving time
changes (0=off, 1=on)
y = diagnostic events
in system log (1=yes,
0=no)
w = power direction
(0=view as load, 1=view
as generator)
f = flip power factor
sign (1=yes, 0=no)
1
753F - 753F 30016 - 30016 Full Scale Current (for load % bar graph) UINT16 0 to 9999 none If non-zero and user
settings bit g is set, this
value replaces CT nu-
merator in the full scale
current calculation.
1
7540 - 7547 30017 - 30024 Meter Designation ASCII 16 char none
8
7548 - 7548 30025 - 30025 Reserved
Set to 0. 1
dddd = reply delay (*
50 msec)
ppp = protocol (1-Mod-
bus RTU, 2-Modbus
ASCII, 3-DNP)
bbb = baud rate (1-9600,
2-19200, 4-38400,
6-57600)
7549 - 7549 30026 - 30026 COM2 setup UINT16 bit-mapped ----dddd -ppp-bbb 1
754A - 754A 30027 - 30027 COM2 address UINT16 1 to 247 none
1
754B - 754B 30028 - 30028 Limit #1 Identifier UINT16 0 to 65535
Use Modbus address as
the identifier (see notes
7, 11, 12).
1
754C - 754C 30029 - 30029 Limit #1 Out High Setpoint SINT16 -200.0 to +200.0 0.1% of full scale Setpoint for the "above"
limit (LM1), see notes
11-12.
1
754D - 754D 30030 - 30030 Limit #1 In High Threshold SINT16 -200.0 to +200.0 0.1% of full scale Threshold at which
"above" limit clears;
normally less than or
equal to the "above"
setpoint; see notes
11-12.
1