1 Description of the Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-…
1.6 Functionality
24 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
Table 3 Assignment of the Ethernet interface
Ethernet (patch) cable
The connecting cable to be selected depends on the the ambient conditions
at the installation location (interference, flexibility, transmission speed).
Use standard Ethernet (patch) cables with RJ45 connectors of category
Cat 5 or higher only. (IEC/EN61131-2, EN50178)
Maximum cable length: 100 m.
If the network covers a longer distance, use the required appropriate
infrastructure components.
Observe the installation guidelines for (Ethernet) wiring in ISO/IEC 11801
and EN 50173.
To establish communications between Modular PLCs XControl: XC-104-…,
XC-204-…, XC-303-… and the programming device, follow the description for
your connected device.
Default IP addresses
The Ethernet interfaces are delivered with the following IP addresses by
default:
Subnet mask: 255.255.255.0
RJ45 socket PIN Ethernet 10/100 MBit Ethernet 1000 MBit
8
BI–_D4
7
BI+_D4
6 Rx– Rx–_D2
5
BI–_D3
4
BI+_D3
3
Rx+ Rx+_D2
2 Tx– Tx–_D1
1
Tx+ Tx+_D1
CAUTION
FORCES ON THE ETHERNET INTERFACE
Communications may be affected, and the connection's
mechanical components may be damaged, if the Ethernet inter-
face is subjected to strong vibrations or the RJ45 plug-in con-
nection is subjected to pulling.
Protect the RJ45 plug-in connection from strong vibrations.
Protect the RJ45 plug-in connection from tensile forces at
the socket.
Interface XC-303-… XC-204-… XC-104-…
ETH0 192.168.119.248 192.168.119.204 192.168.119.104
ETH1 192.168.137.248 DHCP
ETH2 192.168.138.248