1 Description of the Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-…
1.6 Functionality
24 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
Table 3 Assignment of the Ethernet interface
Ethernet (patch) cable
The connecting cable to be selected depends on the the ambient conditions
at the installation location (interference, flexibility, transmission speed).
• Use standard Ethernet (patch) cables with RJ45 connectors of category
Cat 5 or higher only. (IEC/EN61131-2, EN50178)
• Maximum cable length: 100 m.
If the network covers a longer distance, use the required appropriate
infrastructure components.
• Observe the installation guidelines for (Ethernet) wiring in ISO/IEC 11801
and EN 50173.
To establish communications between Modular PLCs XControl: XC-104-…,
XC-204-…, XC-303-… and the programming device, follow the description for
your connected device.
Default IP addresses
The Ethernet interfaces are delivered with the following IP addresses by
default:
Subnet mask: 255.255.255.0
RJ45 socket PIN Ethernet 10/100 MBit Ethernet 1000 MBit
8
– BI–_D4
7
– BI+_D4
6 Rx– Rx–_D2
5
– BI–_D3
4
– BI+_D3
3
Rx+ Rx+_D2
2 Tx– Tx–_D1
1
Tx+ Tx+_D1
CAUTION
FORCES ON THE ETHERNET INTERFACE
Communications may be affected, and the connection's
mechanical components may be damaged, if the Ethernet inter-
face is subjected to strong vibrations or the RJ45 plug-in con-
nection is subjected to pulling.
• Protect the RJ45 plug-in connection from strong vibrations.
• Protect the RJ45 plug-in connection from tensile forces at
the socket.
Interface XC-303-… XC-204-… XC-104-…
ETH0 192.168.119.248 192.168.119.204 192.168.119.104
ETH1 192.168.137.248 DHCP –
ETH2 192.168.138.248 – –