1 Description of the Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-…
1.6 Functionality
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 25
1.6.4.4 RS485
The serial RS-485 interface (X3) depends on the device model.
The serial RS-485 interface (X3) can be used to connect an external display
device, for example.
The RS-485 connection can be used to connect to another PLC as a Modbus
RTU master or Modbus RTU device. The protocol supports EVEN, ODD, and
NONE parity, as well as 1 or 2 stop bits, and is accordingly in conformity with
the CODESYS serial adapter.
Screened twisted-pair cables must be used.
Configuration: X3 plug connector, 3-pin, spring-loaded plug-in terminal block
See also:
•Functionality Page 18
Technical data Page 172
XControl
RS485
serial interface for Modbus RTU
XC-303-…
1)
XC-204-C20-002
XC-204-C21-001
XC-204-C11-003
XC-204-C10-000
XC-104-…
1) Galvanically isolated from the system power supply
Adjustable baud rates
[bauds]
Maximum possible cable length
1200
1200 m
2400
4800
9600
19200
38400
576000
115200