417101774_EMP_KKS_E60_E.doc - 54 - Rev. 8-03.10
10.4 Calibration
10.4.1 Overview
The procedure and display during the calibration process differ depending on whether or not
an oval gear meter is connected.
Fig. 10.53
Calibration pump:
• see chapter 10.4.2
Calibration pump with
oval gear meter:
• see chapter 10.4.3
10.4.2 Calibration pump
10.4.2.1 Preparation
Fig. 10.54
# Connect the pump ready for operation
on the pressure side (see chapter 7
“Installing the device”).
# Fill a suitable measuring cylinder and
insert the suction line or suction and
return line.
NOTE
The volume of the measuring cylinder should be 1/50 of the metering pump rate in litres/h.
During this process, the suction line must not change its position.
The calibration of the metering pump is only valid for the currently set stroke length setting.
After changing the stroke length, the calibration must be performed again.