19 Liebert
®
CW
™
System Design Manual
CW114
10.0 HP
FLA 136.5 128.8 64.7 52.7 57.4 50.2 25.6 22.6 109.9 106.6 53.1 41.1 30.8 28.0 14.0 11.0
WSA 170.6 161.0 80.9 65.9 71.8 62.8 32.0 28.3 137.4 133.3 66.4 51.4 38.5 35.0 17.5 13.8
MFCB 175 150 80 60 90 80 40 35 125 125 70 50 60 60 30 20
CW114
15.0 HP
FLA 151.9 142.8 71.7 58.7 72.8 64.2 32.6 28.6 125.3 120.6 60.1 47.1 46.2 42.0 21.0 17.0
WSA 189.9 178.5 89.6 73.4 91.0 80.3 40.8 35.8 156.6 150.8 75.1 58.9 57.8 52.5 26.3 21.3
MFCB 200 175 90 70 125 110 50 45 175 150 80 60 100 90 45 35
CW114
20.0 HP
(Upflow only)
FLA 165.1 154.8 77.7 63.7 86.0 76.2 38.6 33.6 138.5 132.6 66.1 52.1 59.4 54.0 27.0 22.0
WSA 206.4 193.5 97.1 79.6 107.5 95.3 48.3 42.0 173.1 165.8 82.6 65.1 74.3 67.5 33.8 27.5
MFCB 225 200 110 90 150 125 70 60 200 200 90 70 125 110 60 45
Table 3-2 Electrical data—Forward-curved Blowers, 60Hz systems (continued)
Models / Motor
HP Volts
Reheat/Humidifier No Reheat/Humidifier Reheat/No Humidifier No Reheat/No Humidifier
208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575