Cabinet and Floor-planning Dimensions —Downflow Models with Forward-curved Blowers
37 Liebert
®
CW
™
System Design Manual
Figure 4-14 Cabinet and floor-planning dimensions,
downflow, CW106 and CW114 with forward-curved blowers
Chilled
Water
Model
Dimensional Data inches (mm)
Net Weight
lb (kg)ABCDEFGHJK
CW089
122
(3099)
118
(2997)
35
(889)
31
(787)
120
(3048)
33
(838)
35-5/8
(905)
32
(813)
94
(2388)
2.88
(73)
1925 (873)
CW106 1785 (810)
CW114 1925 (873)
G
OVERALL
C
CABINET
A
OVERALL
76"
1930mm
MODELS WITH PRE-FILTERS
76"
1930mm
9"
229mm
B FILTER PLENUM
AIR RETURN
H
DUCT
FLANGE
B
DUCT
FLANGE
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS
AND FILTER REMOVAL
NOTE:
1. FILTERS ARE ACCESSIBLE
THRU TOP OF UNIT ONLY.
2. ELECTRICAL CONNECTIONS
CAN BE MADE FROM TOP
OR BOTTOM OF UNIT.
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS
AND FILTER REMOVAL
BOTTOM VIEW
33"
838mm
K
E
J
29 1/2"
749mm
27 1/2"
698mm
28 7/8"
733mm
16 1/4"
413mm
Typ.
Front of Unit
Standard Piping
Opening
DPN003834
Rev. 0