EasyManua.ls Logo

Emerson CW026 - Figure 4-14 Cabinet and Floor-Planning Dimensions, Downflow, CW106 and CW114 with Forward-Curved Blowers

Emerson CW026
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cabinet and Floor-planning Dimensions —Downflow Models with Forward-curved Blowers
37 Liebert
®
CW
System Design Manual
Figure 4-14 Cabinet and floor-planning dimensions,
downflow, CW106 and CW114 with forward-curved blowers
Chilled
Water
Model
Dimensional Data inches (mm)
Net Weight
lb (kg)ABCDEFGHJK
CW089
122
(3099)
118
(2997)
35
(889)
31
(787)
120
(3048)
33
(838)
35-5/8
(905)
32
(813)
94
(2388)
2.88
(73)
1925 (873)
CW106 1785 (810)
CW114 1925 (873)
G
OVERALL
C
CABINET
A
OVERALL
76"
1930mm
MODELS WITH PRE-FILTERS
76"
1930mm
9"
229mm
B FILTER PLENUM
AIR RETURN
H
DUCT
FLANGE
B
DUCT
FLANGE
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS
AND FILTER REMOVAL
NOTE:
1. FILTERS ARE ACCESSIBLE
THRU TOP OF UNIT ONLY.
2. ELECTRICAL CONNECTIONS
CAN BE MADE FROM TOP
OR BOTTOM OF UNIT.
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS
AND FILTER REMOVAL
BOTTOM VIEW
33"
838mm
K
E
J
29 1/2"
749mm
27 1/2"
698mm
28 7/8"
733mm
16 1/4"
413mm
Typ.
Front of Unit
Standard Piping
Opening
DPN003834
Rev. 0

Table of Contents

Related product manuals