Dimensions
Liebert
®
CW
™
System Design Manual 36
4.4 Cabinet and Floor-planning Dimensions
—Downflow Models with Forward-curved Blowers
Figure 4-13 Cabinet and floor-planning dimensions, downflow,
CW026 - CW084, with forward-curved blowers
Chilled
Water
Model
Dimensional Data inches (mm) Net
Weight
lb (kg)ABCD E F G H
CW026
50 (120)
46
(1168)
35 (889) 32 (813)
48 (1219)
35 5/8
(905)
31
(787)
34 (856)
760 (345)
CW038 795 (361)
CW041 855 (388)
CW051
74
(1880)
70
(1778)
72 (1829) 56 (1411)
1090 (494)
CW060 1115 (524)
CW076
99
(2515)
97 (2464) 78 (1994)
1320 (599)
CW084 1420 (644)
UNIT DIMENSIONAL DATA
C
CABINET
D
AIR
RETURN
A
OVERALL
B AIR
RETURN
MODELS W/ PRE-FILTERS
F PLENUM
OVERALL
G
AIR RETURN
A
UNIT & PLENUM OVERALL
B
AIR RETURN
AIR DISCHARGE OPENINGS
72"
1829mm
72"
1829mm
9"
229mm
F
OVERALL
FRONT OF UNIT
FRONT OF UNIT
FRONT OF UNIT
SHADED AREA INDICATES A RECOMMENDED
CLEARANCE OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS AND FILTER REMOVAL
ON ALL CW026-CW084 UNIT TYPES
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS AND
FILTER REMOVAL ON ALL
CW026-CW084 UNIT TYPES
NOTES:
1. MINIMUM CLEARANCE OF 24" (610mm) REQUIRED BELOW
THE UNIT TO LOWER THE FANS. FANS MAY ALSO REMAIN
IN UNIT IF DESIRED.
2. VIEWS OF AIR DISCHARGE OPENINGS ARE FROM INSTALLER'S
POINT OF VIEW.
CW026-041
E
H
33"
838mm
31"
795mm
16"
411mm
STANDARD PIPING
OPENING
ELECTRICAL
OPENINGS
CW051-060
E
H
33"
838mm
31"
795mm
16"
411mm
ELECTRICAL OPENINGS
STANDARD
PIPING
OPENING
CW076-084
E
H
33"
838mm
31"
795mm
16"
411mm
STANDARD PIPING
OPENING
ELECTRICAL
OPENINGS
DPN003749
Rev. 0