EasyManua.ls Logo

Emerson CW026 - Figure 5-13 Piping Connections, Upflow, CW106 and CW114

Emerson CW026
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Piping Connections—Upflow Models
65 Liebert
®
CW
System Design Manual
Figure 5-13 Piping connections, upflow, CW106 and CW114
NOTE: Install all piping
per local codes.
UNIT FIELD PIPING LOCATIONS
Piping stubbed out inside unit end compartment for field
connection through 13" x 6-1/2" (330 x 165mm) opening as
shown. Piping may also exit through bottom of end
compartment by field cutting an opening in a suitable
location.
A
- Chilled Water Supply Line.
2-5/8" O.D. CU on 3 way
front return units only.
1/4" OD CU Humidifier Water
Supply Line.
UNIT LEFT
END PANEL
1" (25mm) REAR PANEL
Condensate Drain. Field pitch a min. of
1/8" (3mm) per ft. (305mm). 1-1/4" NPT for units without
a factory installed condensate pump. 1/2" OD CU for
units with factory installed condensate pump. Do not
install an external trap.
B
- Chilled Water Return Line.
2-5/8" O.D. CU
3"
76mm
7 1/2"
190mm
13"
330mm
A
- Chilled Water Supply Line
2-5/8" O.D. CU on all units
except 3 way front return.
DPN001669
Rev. 1

Table of Contents

Related product manuals