Cabinet and Floor-planning Dimensions—Downflow Models with EC Fans
27 Liebert
®
CW
System Design Manual
Figure 4-4 Cabinet and floor-planning dimensions, downflow, CW089, CW106 and CW114 with EC fans
Chilled
Water
Model
Dimensional Data, inches (mm)
Dry Weight
lb (kg)ABCD E F GHJK
CW089
122
(3099)
118
(2997)
35 (889) 31 (787)
120
(3048)
33 (838)
35-5/8
(905)
32 (813)
94
(2388)
2.88 (73)
1925 (873)
CW106 1785 (810)
CW114 1925 (873)
NOTE: "ELECTRICAL OPENING" IS ALSO USED FOR DRAIN CONNECTION
OF OPTIONAL STEAM GENERATING CANNISTER HUMIDIFIER.
G
OVERALL
C
CABINET
A
OVERALL
76"
1930mm
MODELS WITH PRE-FILTERS
76"
1930mm
9"
229mm
B FILTER PLENUM
AIR RETURN
H
DUCT
FLANGE
B
DUCT
FLANGE
BOTTOM VIEW
E
J
28"
711mm
28"
711mm
28"
711mm
31"
787mm
TYP.
33"
838mm
K
FRONT OF UNIT
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS
AND FILTER REMOVAL
STANDARD PIPING
OPENING
ELECTRICAL
OPENINGS
NOTE:
1. FILTERS ARE ACCESSIBLE
THRU TOP OF UNIT ONLY.
2. ELECTRICAL CONNECTIONS
CAN BE MADE FROM TOP
OR BOTTOM OF UNIT.
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS
AND FILTER REMOVAL
NOTE:
MINIMUM CLEARANCE OF 24" (610mm) REQUIRED BELOW
THE UNIT TO LOWER FANS. FANS MAY ALSO REMAIN IN
UNIT IF DESIRED.
DPN003193
Rev. 2