E300 Design Guide 373
Issue Number: 1
Setting Logic Function 1 Output Invert (K06) inverts the output of logic function 1.
Logic Function 1 Delay (K07) defines the delay at the output of logic function 1. If Logic Function 1 Delay (K07) is positive then the output does not
become 1 until the input to the delay has been at 1 for the delay time. If Logic Function 1 Delay (K07) is negative then the output remains at 1 until the
input to the delay has been 0 for the delay time.
Logic Function 1 Destination (K08) defines the output destination of logic function 1.
K06 Logic Function 1 Output Invert
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate 4 ms read
Display Format Standard Decimal Places 0
Coding RW
K07 Logic Function 1 Delay
Mode Open-Loop, RFC-A, RFC-S
Minimum -25.0 Maximum 25.0
Default 0.0 Units s
Type 16 Bit User Save Update Rate 4 ms read
Display Format Standard Decimal Places 1
Coding RW
Logic function delay
Delay input
Delay input
Delay output
Delay output
Delay parameter> 0
Delay parameter< 0
K08 Logic Function 1 Destination
Mode Open-Loop, RFC-A, RFC-S
Minimum A00 Maximum AB99
Default A00 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Menu Param Alpha Numeric Decimal Places 3
Coding RW, DE, PT, BU