EasyManua.ls Logo

Emerson X-STREAM XE - Page 525

Emerson X-STREAM XE
536 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Emerson Process Management GmbH & Co. OHG A-43
X-STREAM XE
Instruction Manual
HASXEE-IM-HS
10/2012
A
Appendix
PLCQuickReferenceCard
Rev.201010
ExampleProgram2
#### First program line MUST begin with ‘####’
#-Example for Timer 1---------------------
TMR_MODE 1 OFFDELAY;
TMR_DURATION 1 5; delay 5 sec
#-Example for Timer 2---------------------
TMR_MODE 2 ONDELAY;
TMR_DURATION 2 5; delay 5 sec
#-Example for Timer 3---------------------
TMR_MODE 3 REPPULSE;
TMR_DURATION 3 5; pulse width 5 sec
TMR_PERIOD_CNT 3 20; periode 20 sec
#-Example for Timer 4---------------------
TMR_MODE 4 SINGLEPULSE;
TMR_DURATION 4 5; pulse width 5 sec
#-Example for Timer 5---------------------
TMR_MODE 5 RETRIGSPULSE;
TMR_DURATION 5 5; pulse width 5 sec
#-Example for Timer 6---------------------
TMR_MODE 6 INHIBSPULSE;
TMR_DURATION 6 10; pulse width 10 sec
#-Example for Timer 7---------------------
TMR_MODE 7 CLKTRGPULSE;
TMR_DURATION 7 5; pulse width 5 sec
TMR_PERIOD_CNT 7 10; pulse trigger is repeated each 10 minutes
TMR_TRIG_TIME 7 2009,10,26,17,00; start triggering Oct26 2009, 05:00 pm
#-Example for Timer 8---------------------
TMR_MODE 8 COUNTER;
TMR_PERIOD_CNT 8 10; preset count value = 10
#--------------------------------
LOAD DI1; Digital Input#1
STO T1I1,T2I1,T3I1; feed Input1 of Timers1..3 with this state
STO R9; assign Digital Input#1 also to Result#9
LOAD DI5; load Digital Input#2
STO T1I2,T2I2,T3I2; feed Input2 of Timers1..3 with this state
#--------------------------------
LOAD T1; read Timer 1 output
STO R1; store as Result#1
#--------------------------------
LOAD DI5; read Digital Input #5
IF R10,R2; if DI5 then load Result#10 else load Result#2
CALL A110; simulate an 'External Failure" of Ch1 if loaded with '1' state
LOAD T3; read Timer 3 output
CALL A311; simulate an "MaintRequ" of Ch3 if loaded with '1' state
#--------------------------------
LOAD S62; CalcA rslt Lo
STO R3; store as Result#3
LOAD S208; Ch2 calibrating
STO R4; store as Result#4
END; Program end
A.7 PLC Quick Reference

Table of Contents

Related product manuals