50 FDUL/VFXR/FDUG/VFXG/AFR/AFG Main features CG Drives & Automation, 01-7318-01r1
7.20.1.2 Reset and Autoreset
operation
If the AFR/AFG drive is in Stop Mode due to a trip
condition, the AFR/AFG drive can be remotely reset by a
pulse (“low” to “high” transition) on the Reset input, default
on DigIn 8.
Depending on the selected control method, a restart takes
place as follows:
7.20.1.2.1 Level-control
If the Run inputs remain in their position the AFR/AFG
drive will start immediately after the Reset command is
given.
7.20.1.2.2 Edge-control
After the Reset command is given a new Run command
must be applied to start the AFR/AFG drive again.
Autoreset is enabled if the Reset input is continuously active.
The Autoreset functions are programmed in menu
“Autoreset [250]”.
7.20.1.3 Run Inputs Level-controlled
The inputs are set as default for level-control. This means
that an input is activated by making the input continuously
“High”. This method is commonly used if, for example,
PLCs are used to operate the AFR/AFG drive.
The examples given in this and the following paragraphs
follow the input selection shown in Fig. 47.
Fig. 47 Example of wiring for Run/Stop/Enable/Reset inputs
The Enable input must be continuously active in order to
accept any run-right or run-left command. If both RunR
and RunL inputs are active, then the AFR/AFG drive stops.
Fig. 48 gives an example of a possible sequence.
Fig. 48 Input and output status for level-control
7.20.1.4 Run Inputs Edge-controlled
Menu “[21A] Level/Edge” must be set to Edge to activate
edge control. This means that an input is activated by a
“low” to “high” transition or vice versa.
See Fig. 47. The Enable and Stop input must be active
continuously in order to accept any run-right or run-left
command. The last edge (RunR or RunL) is valid. Fig. 49
gives an example of a possible sequence.
Fig. 49 Input and output status for edge-control
NOTE: If the control commands are programmed for
Keyboard control or Com, Autoreset is not possible.
CAUTION!
Level-controlled inputs DO NOT comply with
the Machine Directive, if the inputs are
directly used to start and stop the machine.
X1
1
12
22
11
2
3
4
5
6
7
8
9
10
13
14
15
16
17
18
19
20
21
Stop
Reset
+24 V
RunL
RunR
Enable
NOTE: Edge-controlled inputs comply with the
Machine Directive (see Chapter 8. page 51), if the
inputs are directly used for starting and stopping the
machine.
INPUTS
OUTPUT
STATUS
ENABLE
STOP
RUN R
RUN L
Right rotation
Left rotation
Standstill
INPUTS
ENABLE
STOP
RUN R
RUN L
OUTPUT
STATUS
Right rotation
Left rotation
Standstill