CG Drives & Automation 01-7318-01r1 Functional description 77
Over volt G [
254
]
Delay time starts counting when the fault is gone When the
time delay has elapsed, the alarm will be reset if the function
is active.
Over volt [
255
]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Power Fault [
258
]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active
.
Undervoltage [
259
]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active
.
PT100 [
25C
]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
PTC [
25E
]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
External Trip [
25G
]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication Error [
25I
]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s